25 A over 25 metres
- Design current
- 25 A
- One-way run
- 25 m
- System voltage
- 230 V
- Permitted voltage drop
- 3%
- Conductor
- Copper
- Installation
- In conduit
Conductor size required5.21
25 / (6 x 0.8); 2 x 1.68e-8 x 25 x 25 / (230 x 0.03)
Open this exampleConductor size from both current capacity and voltage drop. Long runs are limited by drop rather than by current, which is why a cable rated for the load can still be too small.
Also called: cable sizing calculator, conductor size calculator.
5.21 mm² required, so use the next standard size of 6 mm². Current capacity alone would allow 5.21 mm², but the 25 m run needs 3.04 mm² to stay within 3%. Current capacity is the binding constraint here, not voltage drop.
Two constraints apply and the larger governs. Current capacity depends on how the cable sheds heat, so a conductor in conduit or buried carries less than the same conductor clipped in free air. Voltage drop depends on the run length and binds on anything long. On a short run the current rating decides; past twenty or thirty metres the drop usually takes over, and sizing on ampacity alone leaves the load undervolted.
the conductor must satisfy both current capacity and voltage drop, and the larger requirement winsEach of these is asserted on every build. If a change to the engine ever moved one of these answers, the build would fail before the page could print it.
Conductor size required5.21
25 / (6 x 0.8); 2 x 1.68e-8 x 25 x 25 / (230 x 0.03)
Open this exampleConductor size required24.35
boundary: where the constraint switches
Open this exampleFormula version 1.0.0 · definition 1.0.0 · United States · Report a problem with this calculator