20 A over 30 metres in 4 mm²
- Current
- 20 A
- One-way run length
- 30 m
- Conductor cross section
- 4 mm²
- System voltage
- 230 V
- Conductor
- Copper
- System
- Single phase
Voltage drop5.04
1.68e-8 x 30 x 2 / 4e-6
Open this exampleVoltage drop over a cable run. The factor most often missed is that current flows out and back, so the conductor length is twice the run, and long runs fail on drop well before they fail on current rating.
Also called: cable size calculator, volt drop calculator.
5.04 V over 30 m, which is 2.19% of 230 V. That is within the three percent commonly allowed for a final circuit. The minimum conductor for a 3% limit is 2.92 mm², and 100.8 W is lost as heat in the cable.
Resistance is resistivity times length over cross section, and the length is twice the one-way run because the current returns. Three-phase uses root three rather than two, since the return is shared. The practical point is that a cable rated for the current can still be inadequate: on a long run the drop makes motors run hot and lights dim, and three percent for a final circuit is the usual limit. Aluminium has about 1.6 times the resistivity of copper, so it needs a larger section for the same drop.
the factor of two is the return path: current flows out and backEach of these is asserted on every build. If a change to the engine ever moved one of these answers, the build would fail before the page could print it.
Voltage drop5.04
1.68e-8 x 30 x 2 / 4e-6
Open this exampleVoltage drop8.46
boundary: 1.68 times the copper resistivity
Open this exampleFormula version 1.0.0 · definition 1.0.0 · United States · Report a problem with this calculator